A controller or transmitter housing is judged twice: on the day an electrician mounts and wires it, and every time a technician opens it afterwards. Neither of them has read your datasheet. They have a screwdriver, maybe gloves, sometimes a ladder, and the housing either makes the job obvious or makes it slow.
This post follows the housing in the order the installer meets it: mounting, cable entry, terminals, cover and labels. Along the way are the rules we apply when we build process control housings in sheet plastic.
Mount the empty housing first
Installers want to fix the base to the wall or panel before the electronics go in, or with them lifted out. Put the mounting points where they can be reached with the cover off and the board in place, or outside the housing altogether, so a slipped drill or concrete dust never reaches the board.
| Mounting | Suits | Housing features | Watch for |
|---|---|---|---|
| Wall, keyholes on the back | Light units where a clean front matters | Keyhole slots sized to the screw head | The installer cannot see the screws; side keyholes are easier to reach |
| Wall, side flanges | Heavier units, vibration, uneven walls | Flanges with holes, part of the main housing so they keep its rigidity | Room for a nut driver beside the housing |
| Panel cutout | Controllers and meters an operator reads | Front bezel over the cut edge, sleeve behind, clamps from the rear | Standard bezels of 48 × 48, 48 × 96 and 96 × 96 mm fit cutouts of 45 × 45, 45 × 92 and 92 × 92 mm |
| DIN rail | Modules inside a control cabinet | DIN clip fitted as hardware on the back | Terminals top and bottom, facing the wireways; depth to the cabinet door |
Panel-mount instruments are worth building to those standard DIN sizes, because panel builders already cut those openings and a replacement drops into the old hole. A DIN-rail module clips to standard 35 mm top-hat rail with off-the-shelf clips, which cost less than a custom feature. Our wall mount enclosures page shows the keyhole and flange options in more detail.
Cable entry: choose the face, then the gland
On a wall unit, bring cables in through the bottom face. Water on a cable then runs away from the housing instead of toward the gland, and the cable hangs from the gland rather than pulling on the terminals. Top entry is the last resort.
A gland seals against a flat outside face and is clamped by a locknut inside, so each one needs a flat land at least as wide as the locknut across its corners, clear of any bend. Space neighbors far enough apart for a wrench. Metric glands such as M16, M20 and M25 are common in Europe; in North America many field devices take 1/2-inch NPT conduit entries. Check thread length against wall thickness: a gland that suits 3 mm sheet may leave too little thread for the locknut on a 6 or 8 mm wall.
A separate gland plate solves several problems at once. It can be thinner than the body, it carries every entry so product variants differ by one part, and a blank plate can be drilled by the installer on site. Inside, add a cable-tie point a short distance behind each entry, so a pulled cable loads the tie and not the terminal. Sealing is its own subject; our post on plastic housings for harsh plant environments covers IP ratings and gaskets.
Terminals the technician can see and reach
Put the terminal blocks nearest the cable entries, screw heads facing the opening, with room in front to bend a conductor into place. A technician should be able to land a wire without reaching past the board. Many field transmitters solve this with two compartments, one for wiring and one for electronics, and the same split works in a fabricated housing: a bonded internal wall, or a flat inner cover over the electronics that leaves only the terminals exposed.
That inner cover is the best place for information. It is a flat machined plate, so it can carry the terminal map, the wiring diagram and the loop polarity printed on its face, exactly where the technician is looking. Keep mains and low-voltage signal terminals on opposite sides of a barrier, and print which side is which. Internal brackets and shelves for relays, supplies and terminal strips are machined and bonded in place, as on our custom electrical enclosures.
Covers that open the same way every time
How the cover opens sets the length of every service visit. Three patterns cover most process control housings:
- Hinged door with a turn latch. Nothing comes loose and nothing drops off a ladder; the door stays closed and locked until access is needed. Hinge it so the open door clears the cable entries and the technician’s view of the terminals.
- Screwed lid on brass inserts. A self-tapping boss suits a screw driven once or twice. A lid opened at every calibration needs heat-staked brass inserts, which take repeated service. Use captive screws so nothing falls into the cabinet, and as few as the seal and the lid’s stiffness allow.
- Tool-free door for non-hazardous parts. A battery, a filter or a configuration switch can sit behind a magnetic or slide-in door. In our process a slide-in door needs a frame or an undercut; otherwise use a fastener and an insert.
Where removing a cover exposes hazardous voltage, the product safety standard (IEC 61010-1 for most measurement and control equipment) generally requires a tool or an interlock to open it. That rules out a tool-free latch on the mains compartment and is one more reason to split the housing. Insert sizes and door rules are on our functional features page.

Labels that outlast the installation
A process control housing carries more text than most: the plant’s tag number, terminal numbers, ratings, warnings and sometimes a wiring diagram. Stick-on labels are the usual weak point, lifting at the edges after repeated cleaning and heat cycles. UV digital printing directly on the sheet removes the label and adheres better than silk screen, and engraving suits marks that must survive abrasion.

Three details save trouble later. Leave a flat area for the plant’s own tag, often a metal plate the end user wires or screws on. Recess any nameplate you do apply, and use label stock about .015 in thick so it hides the machine marks in the recess. Check with your certifier before moving the rating plate from a label to direct printing, since certification marks often have to be on a label material the certifier has approved.
Where a fabricated plastic housing is the wrong choice
The process fits indoor controllers, wall-mount displays and gateways, panel instruments and cabinet modules, built in quantities from one to thousands. Some process control housings are not ours to build. Flameproof enclosures for hazardous areas are a different product, typically cast metal, and plastic housings used in classified areas face limits on static charge that start with your certifier. Ingress ratings for washdown or outdoor service are project-specific, so we discuss them at quote stage rather than claim them on a web page. And we build the housing to your design; certifying the device stays with you.